Installation and Operation Manual
●
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 19 of 36
Procedure Steps Display
Starng Display
1. Start at the temperature display.
2. Enter Password 2. The display changes to the MAIN menu display.
F
°
AUTO AUTO
Enter
ADMIN LEVEL
0 0 0 0
Select the
SCHEDULE
menu.
1. From the MAIN menu, press either the or buon to
select SCHEDULE.
2. Press Enter . The SCHEDULE menu opens.
3. Choose SET CLOCK and then press Enter . The SET Clock menu
opens.
Choose a clock
funcon to set.
Choose one of the features in the SET CLOCK menu to change the
date, me, or Daylight Saving Time (DST) seng.
• DATE—The current calendar date.
• TIME—Time is set according to a 12‑hour clock.
• UTC OFFSET—Enter the me oset, in minutes, between local
standard me and Universal Time Coordinated. The value of the
property ranges from ‑780 to +780 seconds. The me zones to
the west of the zero degree meridian are posive values; those
to the east are negave values. The value of the UTC Oset
property is subtracted from the UTC received in a UTC Time
Synchronizaon service request to calculate the correct local
standard me.
• DST ENABLE—Set to TRUE to enable Daylight
• Saving Time and FALSE to use standard me year around.
• DST AUTO—When set to TRUE, the EZstat automacally
calculates the start and end dates from relave dates. For
example, set DST START to the rst Sunday in March instead of a
calendar date.
• DST START and DST END—Enter the dates and me to begin
observing DST. If DST AUTO is set to TRUE the dates are relave;
if set to FALSE the date is a calendar date.
6.4 Setthemeanddate
Seng the me and date requires entering Password 2.
If the EZstat is connected to a BACnet network that includes a me service master, the me and date are automacally
set to the network me and date.
Setthemeanddate
NOTE