Installation and Operation Manual
●
Fan Coil Controller – EZstat
EC-EZstat
Date: 9-2014 Supersedes: NEW
Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.
Page 4 of 36
3.3 Specicaons
EZstat specicaons are subject to change without noce.
User Interface
The user interface is a color display and with ve push buons. Through the menu driven display, an operator can do the
following:
• Add or change user passwords
• Change setpoints
• Set BACnet addressing
• Set up and commission the installaon
• Congure any available opons
Security
Separate passwords for users and controls technicians.
Display type
• 128 ×128 pixels
• Acve color LCD with LED back lighng
• 0.98 x 1.04 inches (25 x 26 mm)
Inputs and outputs
All inputs and outputs are preprogrammed and applicaon specic. Review wiring label for proper connecons.
Analog inputs
Analog inputs represent BACnet analog input objects and are congured for discharge air temperature, remote
temperature sensor and water temperature sensor. Not all input sensors are applicable or required for all applicaons.
• Sensors are automacally detected
• Inputs accept industry‑standard 10,000 Ω, Type II (Nailor Part# H1‑1989) or Type III (Nailor Part# H1‑0246 and H1‑1764B)
thermistors sensors.
• Input overvoltage protecon up to 24 VAC, connuous. 12‑bit analog‑to‑digital conversion
Analog outputs
Analog outputs are congured to represent BACnet analog objects. The outputs control modulang valves, and variable
speed fans, or other equipment that requires a proporonal input signal.
• Short‑circuit protected
• Loads up to 10 mA at 0–12 VDC
• 8‑bit PWM digital‑to‑analog conversion
Relay outputs
Relay outputs are congured to represent BACnet binary objects. The outputs control On/O valves, speeds for three‑
speed fans, fan start circuits, or electric heat.
• All relay outputs are normally open, SPST, Form “A” relays
• 1 ampere maximum per relay at 24 VAC or VDC for each output. Maximum for all relay outputs is 3 amperes (72VA).
Connectors
• Screw terminal block mounted to back plate
• Wire size 14‑22 AWG
Communicaons—BACnetMS/TP
• Integral peer‑to‑peer BACnet MS/TP network communicaons. Network speeds from 9600 to 76,800 baud.
• Front panel congurable device instance, MAC address, and baud. Automac baud detecon, see the topic Set up the
communicaon. Screw terminal block mounted to back‑plate. Wire size 14–22 AWG
• Meets or exceeds ANSI/ASHRAE BACnet Standard 135‑2008 for Applicaon Specic Controllers